Siemens 6EP1961-2BA00 SITOP select Diagnostic Module

The Siemens 6EP1961-2BA00 is a SITOP select diagnostic module designed to provide selective protection for 24 V DC load circuits. It distributes a single 24 V DC input (up to 40 A) across 4 independently protected output channels, each rated for 10 A and adjustable from 2 to 10 A via potentiometer.

  • Item nº :

    6EP1961-2BA00
  • Pedido (MOQ) :

    1
  • Pagamento :

    EXW
  • Origem do produto :

    Germany
  • Porto de embarque :

    Wuhan, Hubei, China
  • Tempo de espera :

    3-5 days
  • Peso :

    0.200kg
  • Overview

    6EP1961-2BA00 Siemens Simatic PLC Module

    New in stock     

    Origin from Germany

    Payment Method: TT.Western Union

    Shipping Method: DHL\UPS\Fedex\EMS\Others 

    More Brands

    Why Choose Us

    Recommended Models & Related Products

     
     
    Part Number Description Key Difference
    6EP1961-2BA00 SITOP select, 4×10 A, common signal contact (this item) Standard model
    6EP1961-2BA21 SITOP PSE200U, 4×10 A, common signal contact Different form factor
    6EP1961-2BA41 SITOP PSE200U, 4×10 A, single-channel signaling Per-channel diagnostics
    6EP1961-3BA21 SITOP PSE202U Redundancy Module For redundant power systems (different function)

    What's Included

    • 1 × Siemens 6EP1961-2BA00 SITOP select Diagnostic Module

    Note: 24 V DC power supply, input/output cables, and DIN rail are sold separately.

    Why Buy From Us?

    • In Stock – Ready to ship immediately

    • Genuine Siemens Product – Factory original SITOP component, PM300 Active status

    • Warranty Included – Purchase with confidence

    • Technical Support – SITOP selective protection configuration assistance available

    Frequently Asked Questions (FAQ)

    Q1: What is the Siemens 6EP1961-2BA00?

    It is a SITOP select diagnostic module that distributes a 24 V DC input across 4 independently protected output channels, each rated for 10 A and adjustable from 2 to 10 A. It provides selective protection so that a fault on one channel does not affect the others .

    Q2: How does selective protection work?

    Each output channel has an electronic overcurrent trip that isolates only the faulted branch. When a channel trips, the other three channels remain powered and operational. This prevents a single short circuit from bringing down the entire 24 V DC system .

    Q3: What is the adjustable trip current range?

    Each channel can be set from 2 to 10 A via a potentiometer on the module .

    Q4: Does this module have remote reset capability?

    No. This model (6EP1961-2BA00) uses a button on the module for reset. It does not have a remote reset input. For per-channel diagnostics and different signaling options, the 6EP1961-2BA41 variant may be considered .

    Q5: What is the signaling contact used for?

    A common normally open (NO) contact (rated 0.5 A / 24 V DC) provides a group alarm when any output trips. This allows a PLC or monitoring system to receive a single fault notification without per-channel wiring .

    Q6: Can I use this module with a SITOP DC UPS?

    No. Siemens explicitly states that the SITOP select is not designed for operation with the DC UPS module 40 A (6EP1 931-2FC21/-2FC42) .

    Q7: What is the input current rating?

    The input is rated for 40 A at 24 V DC .

    Q8: What is the efficiency and power loss?

    Efficiency is 97% typical, with a power loss of 30 W at rated output .

    Q9: What are the dimensions and weight?

    Dimensions are 190 × 72 × 88.7 mm (H × W × D), with a net weight of 0.200 kg .

    Q10: What is the country of origin and lifecycle status?

    Country of origin is Austria. Lifecycle status is PM300: Active Product .

    Q11: What should I verify before ordering?

    Always verify the exact part number (6EP1961-2BA00 for the standard model), confirm your total load does not exceed 40 A on the input, ensure the adjustable trip range (2–10 A per channel) matches your branch loads, and check that the common signaling contact is sufficient for your monitoring requirements (consider 6EP1961-2BA41 for per-channel signaling).

     